The Charge Grid | Solis S6 Hybrid SeriesProduct Sheet 2026 v2.0 |
|
|
160% PV Input & Up to 21A Current
Supports PV input up to 160% of rated DC power, Dual MPPT (up to 4 strings) & 21A PV input current
|
<10ms UPS & 200% Surge (10s)
Seamless on/off-grid switching in <10ms & 200% overload for 10s in off-grid mode for motors & A/C
|
|
40–60V Battery & Up to 210A
Compatible with Li-ion & Lead-acid batteries (40V–60V), up to 210A charge/discharge & max 6 units in parallel
|
7.0" Industrial LCD & SolisCloud
7-inch LCD screen, generator auto-control, Smart Load management & SolisCloud AI optimisation
|
| ● The Charge Grid • Solis S6 Hybrid Energy Storage Inverters | C10/11 • EN 50549-1 • IP66 • IEC/EN 62109-1/-2 |
|
|
The Charge Grid | Solis S6 Hybrid SeriesProduct Sheet 2026 v2.0 |
|
Solis S6 Hybrid S6-EH1P(3-10)K-L-PLUS
|
Single Phase Low Voltage Energy Storage Inverters • 3 – 10 kW |
Up to 160% PV & 21A MPPT | <10ms Back-up & 200% 10s | Max 6 Units in Parallel | 7.0" LCD & SolisCloud AI |
| ✓Supports PV input up to 160% of the inverter's rated DC power, maximising solar utilisation | ✓Supports up to 21A PV input current, compatible with future higher-power PV modules |
| ✓200% overload for 10s in off-grid mode, ensuring stable startup of motors, water pumps and air conditioners | ✓Seamless on/off-grid switching in under 10ms, guaranteeing an uninterrupted power supply |
| ✓More battery options, compatible with any battery (between 40V–60V) | ✓Supports existing PV grid-tied power connection for export control and off-grid use |
| ✓Multiple methods of generator connection and auto control, enabling flexible local deployment | ✓Support max 6 units in parallel, expanding system capacity |
| ✓Smart Load management, extending backup time for critical loads | ✓Customizable battery backup level for uninterrupted power |
| ✓Supports PV-only off-grid operation, reducing upfront costs | ✓SolisCloud: Smart remote control, AI optimisation, and instant troubleshooting - all in one platform |
| ✓7-inch industrial-grade LCD screen, providing a larger, user-friendly interface for local operation | ✓Ingress protection IP66, for operation in harsh conditions |
| Models | 3K | 3.6K | 4.6K | 5K | 6K | 8K | 9K(21A) | 10K(21A) |
|---|---|---|---|---|---|---|---|---|
| Recommended max. PV array size | 6 kW | 7.2 kW | 9.2 kW | 10 kW | 12 kW | 16 kW | 18 kW | 20 kW |
| Max. usable PV input power | 4.8 kW | 5.76 kW | 7.36 kW | 8 kW | 9.6 kW | 12.8 kW | 14.4 kW | 16 kW |
| Max. input voltage | 500 V | |||||||
| Rated voltage | 330 V | |||||||
| Start-up voltage | 90 V | |||||||
| MPPT voltage range | 90 - 435 V | |||||||
| Max. input current | 16 A / 16 A | 32 A / 32 A | 42 A / 42 A | |||||
| Max. current per DC input | 16 A | 21 A | ||||||
| Max. short circuit current | 20 A / 20 A | 40 A / 40 A | 48 A / 48 A | |||||
| MPPT number / Max. input strings number | 2 / 2 | 2 / 4 | ||||||
| Battery type | Li-ion / Lead-acid | |||||||
| Battery voltage range | 40 - 60 V | |||||||
| Max. charge / discharge current | 70 A | 80 A | 105 A | 112 A | 135 A | 190 A | 200 A | 210 A |
| Number of battery port / Number of BMS port | 1 / 1 | |||||||
| Communication | CAN / RS485 | |||||||
|
|
The Charge Grid | Solis S6 Hybrid SeriesProduct Sheet 2026 v2.0 |
| Models | 3K | 3.6K | 4.6K | 5K | 6K | 8K | 9K(21A) | 10K(21A) |
|---|---|---|---|---|---|---|---|---|
| Rated output power | 3 kW | 3.6 kW | 4.6 kW | 5 kW | 6 kW | 8 kW | 9 kW | 10 kW |
| Max. apparent output power | 3 kVA | 3.6 kVA | 4.6 kVA | 5 kVA | 6 kVA | 8 kVA | 9 kVA | 10 kVA |
| Rated grid voltage | L/N/PE, 220 V / 230 V | |||||||
| Rated grid frequency | 50 Hz / 60 Hz | |||||||
| Rated grid output current | 13.7A / 13.1A | 16.4A / 15.7A | 20.9A / 20A | 22.8A / 21.8A | 27.3A / 26.1A | 36.4A / 34.8A | 40.9A / 39.1A | 45.5A / 43.5A |
| Power factor | > 0.99 (0.8 leading - 0.8 lagging) | |||||||
| THDi | < 3% | |||||||
| Max. input power | 4.6 kW | 5.5 kW | 6.4 kW | 7 kW | 8.8 kW | 11 kW | 13.2 kW | 14.3 kW |
| Input voltage range | 187 - 253 V | |||||||
| Max. input current | 21 A | 25 A | 29 A | 32 A | 40 A | 50 A | 60 A | 65 A |
| Rated output power | 3 kW | 3.6 kW | 4.6 kW | 5 kW | 6 kW | 8 kW | 9 kW | 10 kW |
| Max. apparent output power | 2 times of rated power, 10 s | |||||||
| Back-up switch time | < 10 ms | |||||||
| Rated output voltage | L/N/PE, 220 V / 230 V | |||||||
| Rated frequency | 50 Hz / 60 Hz | |||||||
| Rated output current | 13.7A / 13.1A | 16.4A / 15.7A | 20.9A / 20A | 22.8A / 21.8A | 27.3A / 26.1A | 36.4A / 34.8A | 40.9A / 39.1A | 45.5A / 43.5A |
| Max. AC passthrough current | 35 A | 35 A | 40 A | 40 A | 40 A | 50 A | 60 A | 65 A |
| THDv (@linear load) | < 2% | |||||||
| Max. input power | 3 kW | 3.6 kW | 4.6 kW | 5 kW | 6 kW | 8 kW | 9 kW | 10 kW |
| Rated input current | 13.7A / 13.1A | 16.4A / 15.7A | 20.9A / 20A | 22.8A / 21.8A | 27.3A / 26.1A | 36.4A / 34.8A | 40.9A / 39.1A | 45.5A / 43.5A |
| Rated input voltage | L/N/PE, 220 V / 230 V | |||||||
| Rated input frequency | 50 Hz / 60 Hz | |||||||
| Max. efficiency | 96.2% | |||||||
| EU efficiency | 96.1% | |||||||
| BAT charged by PV / AC max. efficiency | 95.3% / 93.9% | |||||||
| Battery discharged efficiency | 93.8% | |||||||
|
|
The Charge Grid | Solis S6 Hybrid SeriesProduct Sheet 2026 v2.0 |
| Models | 3K | 3.6K | 4.6K | 5K | 6K | 8K | 9K(21A) | 10K(21A) |
|---|---|---|---|---|---|---|---|---|
| Surge protection | Yes | |||||||
| Output over current protection | Yes | |||||||
| Insulation resistance monitoring | Yes | |||||||
| Residual current detection | Yes | |||||||
| Integrated PV switch | Yes | |||||||
| DC reverse-polarity protection | Yes (PV only) | |||||||
| Protection class / Over voltage category | I / II (PV and BAT), III (MAINS and BACKUP and GEN) | |||||||
| Integrated AFCI 2.0 | Optional | |||||||
| Anti-islanding protection | Yes | |||||||
| Dimensions (W × H × D) | 335 × 560 × 253 mm | |||||||
| Weight | 23 kg | 23.5 kg | 23.8 kg | |||||
| Inverter topology | Non-isolated (PV), Isolated (Battery) | |||||||
| Self-consumption | < 40 W | |||||||
| Operating temperature range | -25 ~ +60°C | |||||||
| Relative humidity | 0 - 100% | |||||||
| Ingress protection | IP66 | |||||||
| Noise emission (typical) | < 40 dB(A) | < 65 dB(A) | ||||||
| Cooling concept | Natural cooling | Intelligent redundant fan-cooling | ||||||
| Max. operation altitude | 3000 m | |||||||
| Grid connection standard | C10/11, NRS 097-2-1, IEC 62116, IEC 61727, IEC 60068, IEC 61683, EN 50530, EN 50549-1, MEA, PEA, NBR 16149, NBR 16150, G98, G99, CEI 0-21, NTS 631 TypeA | |||||||
| Safety / EMC standard | IEC/EN 62109-1/-2, EN 61000-6-2/-3 | |||||||
| PV connection | MC4 connector | |||||||
| Battery connection | Terminal Block | |||||||
| AC connection | Terminal Block | |||||||
| Display | 7.0" LCD display & Bluetooth + APP | |||||||
| Communication interface | Standard: WIFI+LAN+Bluetooth, CAN-BMS, CAN-Parallel×2, RS485-Meter, RS485, DRM, DI, DO×2; Optional: 4G | |||||||
|
Integrated Hybrid Ecosystem: Solis S6-EH1P-L-PLUS + Easyway UNIV5200 + GRID-EMS
Direct CAN-BMS communication with 51.2V LiFePO4 battery stacks (such as Easyway UNIV5200 5.22 kWh modules up to 16× in parallel), automatic generator control, <10ms UPS backup switching, and AI Time-of-Use optimisation via SolisCloud and The Charge Grid GEMS.
|
|